Access Control Processing and Host Interface for up to 32Door/Reader Interface, Input Monitor, or Output Control Units.
The HID VertX™ products provide a complete and fully featured hardware/firmware infrastructure for OEM access control software host systems, communicating via industry standard TCP/IP protocol, over 10/100 Mbps Ethernet or the Internet. The V1000 boasts a 32-bit RISC processor running the Linux Operating System. On-board flash memory allows program updates to be downloaded via the network. The V1000 connects up to 32 Door/Reader, Input Monitor, or Output Control Interfaces via two independent RS-485 networks, each network having two sets of input connections for optimum system topology. This architecture minimizes the impact on corporate LANs by using only one TCP/IP address for every 32 interfaces, and by handling low-level transactions on the RS-485 network.
Dimensions 5.8" W x 4.825" H x 1.275" D (147.32 mm x 122.55 mm x 32.38 mm)
Weight: 12.4 oz (.35 kg)
Power Supply Requirements 140 mA @ 12-18 VDC
Cable Distance RS-485 – 4000 feet per network (two independent RS-485 networks) using Belden 3105 (22AWG) 2-twisted pair, shielded 100Ω cable TCP/IP – 300 feet (100 m) to next device, using Category 5 cable, Alpha 9504C or 9504F Input Circuits – 500 feet (150 m), 2-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C (18AWG) Output Circuits – 500 feet (150 m), 2-conductor, using ALPHA 1172C (22AWG) or Alpha 1897C (18AWG) Minimum wire gauge depends on cable length and current requirements.
Operating Environment Indoors, or customer-supplied NEMA-4 Enclosure
Temperature 32° to 122° F (0° to 50° C)
Humidity 5% to 95% relative, non-condensing
Communication Ports RS-485 – two wire. TCP-IP – one port, 10 or 100 Mbps
Certifications UL 294 and UL 1076 Recognized Component for the US CSA 205 for Canada FCC Class A Verification EMC for Canada, EU (CE Mark), Australia (C-Tick Mark), New Zealand, Japan EN 50130-4 Access Control Systems Immunity for the EU (CE Mark)